Commercial

The HS Series R290 air/water inverter heat pumps are designed for high-capacity residential and light commercial applications, combining natural refrigerant technology, wide operating range, and robust system protection. With heating output up to 54.2 kW and hot water temperature up to 75°C, the HS Series delivers reliable performance even in extreme low-temperature environments.

Detailed
Slide to the left to view >

HS Series R290 Air/Water Inverter Heat Pumps

Part 1|Product Overview & Application Positioning

The HS Series R290 air/water inverter heat pumps are engineered for applications requiring higher heating capacity, stable year-round operation, and enhanced system protection. Using R290 natural refrigerant (GWP = 3), the series aligns with current and future environmental regulations while maintaining high energy efficiency. 

Designed for heating, cooling, and domestic hot water production, the HS Series supports a maximum outlet water temperature of up to 75°C, making it suitable for both new installations and renovation projects. The system remains operational at outdoor temperatures down to –25°C, ensuring dependable comfort in cold-climate regions. 

With corrosion-resistant casing treatment and multiple operational protections for heating, cooling, and defrosting, the HS Series is well suited for residential blocks, commercial buildings, and energy-demanding applications where durability and reliability are critical. 

Part 2|Technical Design & Performance Advantages

The HS Series integrates DC inverter technology with a carefully engineered refrigerant circuit to achieve both efficiency and stability. The system reaches ErP energy efficiency class A++, supported by intelligent climate compensation curves that automatically adjust water temperature according to ambient conditions. 

Key Technical Highlights

  • Twin rotary DC inverter compressors, specifically designed for R290 refrigerant and installed in tandem configuration, ensuring smooth capacity modulation and high reliability 

  • EC brushless axial fans with airfoil blades, dynamically and statically balanced to optimize airflow while reducing noise and vibration 

  • Copper-brazed refrigerant circuit, with every unit undergoing pressure testing, leak testing, and online operation testing before leaving the production line 

  • Automatic refrigerant charging system, ensuring precise R290 filling for optimal system performance 

The HS Series also incorporates an intelligent compressor operation compensation function, improving system stability under varying load conditions and reducing unnecessary stress on core components. 

With its high heating output range (up to 54.2 kW), strong low-temperature capability, and integrated system protections, the HS Series represents a robust R290 solution for medium-to-large air-to-water heat pump applications. 


Product Parameters
Slide to the left to view >
Modellnummer /Model NumberHS50V-D
Heizbedingung /Heating Condition 
Heizleistungsspanne /Heat output range(1)kW17.7~ 54.2
Nennheizleistung /Rated heat output(1)kW50.4
Nennleistungsaufnahme /Rated Power consumption(1)kW11.8
COP(1)W/W4.3
Nennheizleistung /Rated heat output(2)kW48.9
Nennleistungsaufnahme /Rated Power consumption(2)kW16.5
COP(2)W/W3.0 
Kühlbedingung/Cooling Condition 
Nennkühlleistung /Rated cool output(3)kW37.5
Nennleistungsaufnahme /Rated Power consumption(3)kW9.1
EER(3)W/W4
Nennkühlleistung /Rated cool output(4)kW34.6
Nennleistungsaufnahme /Rated Power consumption(4)kW11.1
EER(4)W/W3.1
Energieeffizienz/Energy efficiency
SCOP(35℃)W/W4.0 
ErP Stufe (35℃) /ErP Level(35℃)ClasseA++
SCOP(55℃)W/W3.3
ErP Stufe (55℃) /ErP Level(55℃)ClasseA+
Geräuschpegel/Noise level
Schallleistungspegel /Sound power leveldB(A)70
Schalldruckpegel /Sound pressure leveldB(A)58
Ventilatoren/Fans
Nennluftstrom /Nominal air flowm3/h18800
Elektrische Daten/Electrical data
Stromversorgung /Power Supply
400V/3N~/50Hz
Max. Leistungsaufnahme /Max. power inputkW20.74
Max. Betriebsstrom /Max operating currentA31.5
Kompressoren/Compressors
Verdichtertyp /Compressor Type
Twin Rotaty
Verdichter /Compressorsn°2
Kältekreisläufe /Refrigerant circuitsn°1
Kältemittel R290 Füllmenge /Refrigerant R290 filling weightkg3.50 
Produktspezifikation/Product Specification
Maximale Austrittstemperatur des Heizmediums /
Max outlet heating medium temperature
℃75
Rohranschluss /Pipe connectorinchG 1" 1/2
Nennwasserdurchfluss /Rated Water flowm3/h8.5
Nettogewicht /Net Weightkg510
Abmessungen (HxBxT) /Dimensions (HxWxD)mm1980×900×1800